文章摘要
Failure Cause Analysis of ACM Sealing Ring for Building Electrical Equipment
Received:April 07, 2023  Revised:April 07, 2023
DOI:10.12136/j.issn.1000-890X.2025.01.0049
Key Words: acrylate rubber; tensile properties; compression performance; loss factor; failure
Author NameAffiliationE-mail
JIANG Guangming* China Academy of Building Research jiangguangming@yeah.net 
XIN Zhaohui TBEA Shenyang Transformer Group Ltd  
WANG Guangke State Grid Smart Grid Research Institute  
HU Shui Beijing University of Chemical Technology  
JIA Yinghua CARS Jinhua Testing Center Co. Ltd  
XIAO Kaiwei China Academy of Building Research  
Hits: 347
Download times: 127
Abstract:
      The two kinds of acrylate rubber(ACM) sealing rings were removed from building electrical equipment that had not or had leakage failure,and the failure status was observed and the cause of the failure was analyzed.IR and TG analysis indicated that the composition of the two kinds of sealing rings compounds was consistent.Physical properties analysis showed that the hardness and the tensile properties of the failed sealing ring compound were lower,while dynamic mechanical property analysis showed that the cross-linking density of the failed sealing ring compound was lower.To sum up,the leakage failure of the sealing ring may be due to its insufficient vulcanization degree,insufficient strength,deformation during assembly due to compression and reduced oil resistance.